基于时域暂态电压拟合的新能源送出线路故障测距新方法
CSTR:
作者:
作者单位:

(1.南方电网云南电网有限责任公司电力科学研究院 ,云南 昆明 650011;2.武汉理工大学自动化学院 ,湖北 武汉 430070)

作者简介:

通讯作者:

唐金锐(1986—),男,博士,副教授,主要从事电力系统继电保护技术等研究;E-mail:tangjinrui@whut.edu.cn

中图分类号:

TM863

基金项目:

云南电网公司科技项目计划(YNKJXM20222034)


A novel fault location method for renewable energy transmission lines based on time -domain transient voltage fitting
Author:
Affiliation:

(1. Electric Power Research Institute of Yunnan Power Grid Co ., Ltd., China Southern Power Grid , Kunming 650011, China; 2. School of Automation , Wuhan University of Technology , Wuhan 430070, China)

Fund Project:

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
  • |
  • 文章评论
    摘要:

    受新能源机组的控制策略和参数影响,新能源送出线路一旦出现故障,其新能源侧短路电流将表现出幅值受控、相位突变、非工频量占比高等特征,导致传统基于工频量的双端和单端故障测距方法失效。为解决这一问题,给出了故障点前和故障点后的新能源送出线路高阶故障暂态微分方程,构建了基于线路两端时域采样电压和采样电流的故障距离联合求解方程组,结合牛顿 ?拉夫逊和最小二乘法实现时域暂态电压拟合,利用时间窗内的暂态多采样数据实现该高阶非线性微分联合方程组的求解,最终完成送出线路的精确故障测距。结果表明,所提定位方法仅需要新能源送出线路两端三相电压和电流的瞬时采样值,不受电力电子设备变流器的影响,测距误差在5%以内,可避免装设昂贵的行波测距装置,工程易实现。

    Abstract:

    Affected by the control strategy and parameters of renewable energy units,once a fault occurs in a renewable energy transmission line,the short-circuit current on the renewable energy side exhibits characteristics such as controlled amplitude,sudden phase change,and a high proportion of non-power-frequency components,which leads to the failure of traditional double-end and single-end fault location methods based on power-frequency components.To address this problem,higher-order fault transient differential equations of the renewable energy transmission line before and after the fault point were provided.A joint equation system for solving fault distance was constructed based on the time-domain sampled voltages and sampled currents at both ends of the line.The time-domain transient voltage fitting was realized by integrating the Newton-Raphson method and the least squares method.The solution of the higher-order nonlinear differential joint equation system was achieved by using the transient multi-sampling data within the time window,and the accurate fault location of the transmission line was ultimately accomplished.The results indicate that the proposed location method only requires the instantaneous sampling values of three-phase voltages and currents at both ends of the renewable energy transmission line,and is not affected by the converters of power electronic equipment.The location error is within 5%.The installation of expensive traveling-wave location devices can be avoided,and its engineering implementation is easy.

    参考文献
    相似文献
    引证文献
引用本文

张丽,李胜男,王是尧,等.基于时域暂态电压拟合的新能源送出线路故障测距新方法[J].电力科学与技术学报,2026,41(3):59-67.
Zhang Li, Li Shengnan, Wang Shiyao, et al. A novel fault location method for renewable energy transmission lines based on time -domain transient voltage fitting[J]. Journal of Electric Power Science and Technology,2026,41(3):59-67.

复制
分享