    摘要:

    针对多类易混暂态扰动下高阻接地故障 (high imped ance fault,HIF)弱特征难以表征以及漏判风险未被充分 考 虑 等 问 题,提 出 一 种 引 导 多 尺 度 残 差 注 意 力 时 序 表 征 与 风 险 感 知 的 轻 量 梯 度 提 升 机 (light gradient boosting machine,LightGBM )辨识方法。首先,以原始零序电流为输入,依据 HIF 随机燃弧、局部尖峰、半周不对称和非平稳波动等波形机理,构建多尺度残差注意力时序卷积网络,自适应地提取不同时间尺度下的深层判别特征;其次,将深层时序特征输入 LightGBM,并引入面向保护应用的类别风险权重,使分类边界向降低 HIF 漏判方向调整。最后,进行仿真与 10 kV真型试验,验证所提方法的有效性。研究结果表明,所提方法在仿真验证集上的总体辨识准确 率 为 98.19%,HIF 召 回 率 为 99.17%;在 真 型 试 验 独 立 测 试 集 上 的 总 体 辨 识 准 确 率 为 97.69%,HIF 召 回 率 为98.00%。所提方法在多类易混扰动下可有效降低 HIF 漏判风险。

    Abstract:

    To address the difficulty of representing the weak features of high-impedance ground faults (HIFs ) under multiple types of confusing transient disturbances,as well as the insufficient consideration of missed-detection risk,a mechanism-guided identification method based on multi-scale residual attention temporal representation and a risk-aware light gradient boosting machine (LightGBM ) is proposed.First,using the original zero-sequence current as input,a multi-scale residual attention temporal convolutional network is constructed based on the HIF waveform mechanisms of random arcing,local spikes,half-cycle asymmetry,and nonstationary fluctuations to adaptively extract deep discriminative features at different time scales.Second,the deep temporal features are input into LightGBM,and protection-oriented class risk weights are introduced so that the classification boundary is adjusted toward reducing HIF missed detections.Finally,simulation and a 10 kV full-scale test are conducted to verify the effectiveness of the proposed method.The results show that the proposed method achieves an overall identification accuracy of 98.19% and an HIF recall of 99.17% on the simulation validation set.On the independent test set from the full-scale test,the overall identification accuracy and HIF recall are 97.69% and 98.00%,respectively. The proposed method effectively reduces the risk of HIF missed detection under multiple types of confusing disturbances.

    参考文献
    相似文献
    引证文献
引用本文

刘怀舟,刘捃锓,邓丰.面向多类易混扰动的配电网高阻故障机理引导时序表征与风险感知辨识方法[J].电力科学与技术学报,2026,41(4):1-11.
Liu Huaizhou, Liu Junqin, Deng Feng. Mechanism -guided temporal representatio n and risk -aware identification method for high -impedance ground faults in distribution networks under multiple types of confusing disturbances[J]. Journal of Electric Power Science and Technology,2026,41(4):1-11.

复制
分享
相关视频

文章指标
  • 点击次数:
  • 下载次数:
  • HTML阅读次数:
  • 引用次数:
历史
  • 收稿日期:2026-05-01
  • 最后修改日期:
  • 录用日期:
  • 在线发布日期: 2026-09-02
  • 出版日期:
文章二维码