不对称故障下的新能源多馈入系统暂时过电压精确计算方法
CSTR:
作者:
作者单位:

(1.上海电力大学电气工程学院 ,上海 200090;2.浙江大学电气工程学院 ,浙江 杭州 310027 )

作者简介:

通讯作者:

汤波(1984—),男,博士,教授级高级工程师,主要从事新型配电网规划与优化运行、电力系统数据分析等方面的研究;E-mail:tangbo@shiep.edu.cn

中图分类号:

TM712

基金项目:

上海市科委创新行动计划(22dz1206802)


Accurate calculation method for transient overvoltage in multi -infeed renewable power systems under asymmetric faults
Author:
Affiliation:

(1. Faculty of Electrical Engineering , Shanghai University of Electric Power , Shanghai 200090 , China ; 2. College of Electrical Engineering , Zhejiang University , Hangzhou 310027 , China )

Fund Project:

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
  • |
  • 文章评论
    摘要:

    故障恢复阶段的高比例新能源电力系统的 暂时过电压问题日益凸显,但相关研究仍聚焦三相短路故障,对不对称故障场景的研究鲜见。首先,分析不对称故障下新能源机组的暂态特性。其次,构建含负序控制的等效模型,并在单机系统中比较了三相与不对称短路引发的暂时过电压程度。再次,针对多馈入系统中负序控制与机组耦合难以刻画的问题,提出一种基于正负序分量迭代的过电压计算方法。该方法将含负序控制的新能源机组等效为压控电流源,通过迭代求解端口电压与注入电流,实现故障期间及清除后过电压的准确评估。最后,在PSCAD/EMTDC 数值仿真分析平台中进行电磁暂态仿真,验证所提方法的有效性。该方法可为不对称故障下新能源多馈入系统的暂时过电压计算提供参考。

    Abstract:

    During fault recovery,transient overvoltages (TOVs ) have become an increasingly prominent issue in power systems with high penetration of renewable energy sources.However,related research,primarily focusing on three-phase short-circuit faults,rarely addresses asymmetric fault scenarios.This study approaches the issue by analyzing the transient characteristics of renewable energy units under asymmetric faults.Then,it presents an equivalent model incorporating negative-sequence control and compares the severity of TOVs caused by three-phase symmetric and asymmetric short-circuits in a single-unit system.Furthermore,to address the difficulty in characterizing the coupling between generation units and between the units and negative-sequence control in multi-infeed systems,the study proposes an iterative TOV calculation method based on positive- and negative-sequence components.This method models renewable energy units with negative-sequence control as voltage-controlled current sources and accurately evaluates the overvoltages during the fault and after fault clearance by iteratively solving port voltages and injected currents.Finally,electromagnetic transient simulations are conducted on the PSCAD/EMTDC numerical simulation and analysis platform to verify the effectiveness of the proposed method.This method can serve as a reference for calculating TOVs in multi-infeed renewable power systems under asymmetric faults.

    参考文献
    相似文献
    引证文献
引用本文

张璐,黄劼睿,汤波,等.不对称故障下的新能源多馈入系统暂时过电压精确计算方法[J].电力科学与技术学报,2026,41(4):267-277.
Zhang Lu, Huang Jie rui, Tang Bo, et al. Accurate calculation method for transient overvoltage in multi -infeed renewable power systems under asymmetric faults[J]. Journal of Electric Power Science and Technology,2026,41(4):267-277.

复制
分享
相关视频

文章指标
  • 点击次数:
  • 下载次数:
  • HTML阅读次数:
  • 引用次数:
历史
  • 收稿日期:2025-07-18
  • 最后修改日期:
  • 录用日期:
  • 在线发布日期: 2026-09-02
  • 出版日期:
文章二维码