Research and application of field calibration method for the DC electronic voltage transformer in converter stations
Author:
Affiliation:

Clc Number:

TM89

Fund Project:

  • Article
  • |
  • Figures
  • |
  • Metrics
  • |
  • Reference
  • |
  • Related
  • |
  • Cited by
  • |
  • Materials
  • |
  • Comments
    Abstract:

    Due to the lack of corresponding test equipment, key technologies and test procedures, the field accuracy calibration test is not fully carried out for the DC electronic voltage transformer (DCEVT) which is widely used in the power grid at present. Under this circumstance, its theory, transmission mechanism and error source are completely analyzed firstly. Then, for the fact that there is no synchronous signal port accessing in the converter station merging unit. A scheme of synchronous field calibration in different places is proposed, and the development of high accuracy field calibration system and uncertainty analysis is carried out. The proposed method is verified in Yongfu DC project, which provides a reference for the field calibration of DC electronic voltage transformer in converter station in China.

    Reference
    Related
    Cited by
Get Citation

朱梦梦,朱全聪,束洪春,曹 敏,孙 军,董 俊,宋 健,田鑫萃.换流站直流电子式电压互感器现场校准方法研究与工程应用[J].电力科学与技术学报英文版,2020,35(3):179-184. ZHU Mengmeng, ZHU Quancong, SHU Hongchun, CAO Min, SUN Jun, DONG Jun, SONG Jian, TIAN Xincui. Research and application of field calibration method for the DC electronic voltage transformer in converter stations[J]. Journal of Electric Power Science and Technology,2020,35(3):179-184.