The influence analysis of ambient temperature on measurement of UHV transmission line
Author:
Affiliation:

Clc Number:

TM451

Fund Project:

  • Article
  • |
  • Figures
  • |
  • Metrics
  • |
  • Reference
  • |
  • Related
  • |
  • Cited by
  • |
  • Materials
  • |
  • Comments
    Abstract:

    Aiming at the abnormal phenomenon of negative statistical line loss occurring in some interprovincial ultrahigh voltage (UHV) transmission lines under light load, the influence of ambient temperature on measurement of UHV transmission line is analyzed in this paper. Firstly, the UHV transmission line of NanyangJingmen is taken as an example to establish a mathematical model of the influence of temperature on equivalent dividing capacitance of capacitor voltage transformer (CVT). Then, the relationship between the ambient temperature and the equivalent dividing capacitance of CVT is deduced. In the end, based on the historical temperature data, the influence of ambient temperature on the voltage division ratio of CVT is calculated. It is shown that the error of CVT voltage ratio caused by the environmental temperature may result in the negative statistical line loss of UHV transmission line when considering the discrepancies of CVT parameters.

    Reference
    Related
    Cited by
Get Citation

徐静,丁一阳,崔新强,陈玉.环境温度对特高压线路计量的影响分析[J].电力科学与技术学报英文版,2020,35(5):165-170. XU Jing, DING Yiyang, CUI Xinqiang, CHEN Yu. The influence analysis of ambient temperature on measurement of UHV transmission line[J]. Journal of Electric Power Science and Technology,2020,35(5):165-170.