Simulation analysis and experimental research on arc-extinguishing gap of 35 kV transmission line
Author:
Affiliation:

Clc Number:

TM863

Fund Project:

  • Article
  • |
  • Figures
  • |
  • Metrics
  • |
  • Reference
  • |
  • Related
  • |
  • Cited by
  • |
  • Materials
  • |
  • Comments
    Abstract:

    In order to solve the general lightning problems of 35 kV transmission lines, a new arc-extinguishing and lightning protection gap (NALPG) is proposed in this article. So as to verify the feasibility of the device, the principle of arc extinction of the device is discussed, and the mechanism of arc development and extinction is studied. Meanwhile, the electromagnetic transient calculation software is applied to build a 35 kV transmission line model of lightning strike to analyze the transient process of the device after arc quenching. Simulation results show that NALPG has the ability to reduce lightning overvoltage and harmonic components. Then, experimental circuit is constructed to conduct power frequency arc cut off test. The test results show that the entire arc extinction time is only 4.0 ms and the arc does not reignite for a period of time. Until now, the actual lightning protection effect of NALPG shows excellent results in line operation.

    Reference
    Related
    Cited by
Get Citation

孔佳琦,夏志坚,王巨丰,陈舒婷.35kV输电线路灭弧间隙的仿真分析与试验[J].电力科学与技术学报英文版,2022,37(1):202-210. KONG Jiaqi, XIA Zhijian, WANG Jufeng, CHEN Shuting. Simulation analysis and experimental research on arc-extinguishing gap of 35 kV transmission line[J]. Journal of Electric Power Science and Technology,2022,37(1):202-210.

Copy
Share
Article Metrics
  • Abstract:
  • PDF:
  • HTML:
  • Cited by:
History
  • Received:
  • Revised:
  • Adopted:
  • Online: April 01,2022
  • Published: