An improved current‑limiting DC circuit breaker topology
Author:
Affiliation:

(School of Electrical Engineering, Xinjiang University,Urumqi 830017, China)

Clc Number:

TM762

Fund Project:

  • Article
  • |
  • Figures
  • |
  • Metrics
  • |
  • Reference
  • |
  • Related
  • |
  • Cited by
  • |
  • Materials
  • |
  • Comments
    Abstract:

    In response to the problems of high cost and excessive fault current under fault conditions in existing hybrid DC circuit breaker topologies, this paper proposes an improved current limiting DC circuit breaker topology based on the existing traditional DC circuit breaker topology. The current?limiting branch of the topology was connected to the circuit after the fault occured, effectively limiting the rise of fault current. The transfer branch consisted of thyristor and IGBT in series to reduce the number of IGBT.A pre?charged capacitor was used to provide the reverse voltage for the thyristor, and a pre?charged scheme was proposed. The operation principle was analyzed based on the proposed topology, and then the parameters were designed. Finally, a simulation model was built in PSCAD/EMTDC, compared with the breaker with traditional topology, to verify the reliability and economy of the proposed topology.

    Reference
    Related
    Cited by
Get Citation

刘 进,樊艳芳,孙 瑶,王亚强.一种改进型限流式直流断路器拓扑[J].电力科学与技术学报英文版,2023,38(2):30-39. LIU Jin, FAN Yanfang, SUN Yao, WANG Yaqiang. An improved current‑limiting DC circuit breaker topology[J]. Journal of Electric Power Science and Technology,2023,38(2):30-39.