Improved tripping and phase‑separation adaptive autoreclosing strategy suitable for ground fault on double‑circuit transmission lines
Author:
Affiliation:

(School of Electrical Engineering, Xinjiang University, Urumqi 830046, China)

Clc Number:

TM773

Fund Project:

  • Article
  • |
  • Figures
  • |
  • Metrics
  • |
  • Reference
  • |
  • Related
  • |
  • Cited by
  • |
  • Materials
  • |
  • Comments
    Abstract:

    When a ground fault occurs on double-circuit transmission lines, the conventional tripping strategy may inject negative-sequence components into the system. The traditional autoreclosing scheme does not determine the fault feature before the reclosing, and the stability of the power system will be affected if the reclose fails. To solve the above problems, an improved tripping strategy suitable for ground faults on double-circuit transmission lines is proposed, where phase-separation adaptive autoreclosing is used in the tripping strategy. Firstly, by establishing and analyzing the phase-to-phase coupling model of double-circuit transmission lines, an improved tripping strategy that can avoid the injection of negative-sequence components into the power system is proposed. Secondly, the capacitive coupling voltage characteristics are analyzed under transient and permanent faults respectively, and the fault feature identification criteria based on the capacitive coupling voltage of double-circuit transmission lines is proposed. Finally, the improved tripping and closing strategy are combined to form a phase-separation adaptive autoreclosing strategy suitable for ground faults on double-circuit transmission lines. The PSCAD/EMTDC simulation verifies that the proposed phase-separation adaptive autoreclosing strategy can avoid the injection of negative-sequence components into the system and ensure the reclosing success rate of the transmission line under different ground fault types, fault locations and transition resistances.

    Reference
    Related
    Cited by
Get Citation

蒋江波,解 超,李凤婷,尹纯亚.适用于同杆双回线路接地故障改进跳闸与分相自适应重合闸策略[J].电力科学与技术学报英文版,2024,(3):48-57. JIANG Jiangbo, XIE Chao, LI Fengting, YIN Chunya. Improved tripping and phase‑separation adaptive autoreclosing strategy suitable for ground fault on double‑circuit transmission lines[J]. Journal of Electric Power Science and Technology,2024,(3):48-57.

Copy
Share
Article Metrics
  • Abstract:
  • PDF:
  • HTML:
  • Cited by:
History
  • Received:
  • Revised:
  • Adopted:
  • Online: July 25,2024
  • Published: