基于广义S变换和皮尔逊相关系数的新能源接入电网纵联保护
作者:
作者单位:

(1.国网安徽省电力有限公司,安徽 合肥 230022;2.北京四方继保自动化有限公司,北京 100085)

通讯作者:

叶远波(1973—),男,硕士,教授级高级工程师,主要从事电力系统继电保护研究;E?mail:yeyb7079@ah.sgcc.com.cn

中图分类号:

TM73

基金项目:

国家自然科学基金联合基金(U2166205);国家电网有限公司科技项目(521200220009)


Pilot protection for new energy access to power grid based on generalized S transform and Pearson correlation coefficient
Author:
Affiliation:

(1.State Grid Anhui Electric Power Co., Ltd., Hefei 230022, China; 2.Beijing Sifang Automation Co., Ltd., Beijing 100085, China)

  • 摘要
  • | |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • | |
  • 文章评论
    摘要:

    随着新型电力系统建设的推进,分布式新能源容量大幅度提升,越来越多的电力电子设备接入电力系统中,导致短路时送出线的电流幅值受限,相角受控,造成传统的工频继电保护方法不再适用。此外,现有的方法在新能源出力较弱时容易出现保护判据失效的问题。为解决以上问题,提出一种基于广义S变换和皮尔逊相关系数的新能源接入电网纵联保护方法。首先,分别对两端电流使用广义S变换得出频域下的故障特征量;然后,使用皮尔逊相关系数计算两端暂态能量相关程度,进一步辨别区内和区外故障;最后,经过实验表明,所提方法能够满足保护的快速性要求,而且具有较强的耐受过渡电阻能力,该方法不受由新能源电力电子装置接入引起的短路电流新特性影响,能够应用于新能源送出线中。

    Abstract:

    As the construction of new power systems proceeds, the capacity of distributed new energy has greatly increased, and more and more power electronic devices are connected to the power system, resulting in limited current amplitude and controlled phase angle of the transmission lines during short circuits. Therefore, the traditional power frequency relay protection methods are no longer applicable. In addition, existing methods are prone to the failure of protection criteria when the output of new energy is weak. To address these issues, a pilot protection method for new energy access to the power grid based on generalized S transform and Pearson correlation coefficient is proposed. Firstly, the generalized S transform is used to obtain the fault characteristic quantities in the frequency domain for currents at both ends. Then, the Pearson correlation coefficient is utilized to calculate the correlation degree of transient energy at both ends, so as to further identify intra-zone and extra-zone faults. Finally, experiments show that the proposed method can meet the requirements of protection rapidity and has a strong ability to withstand transition resistance. This method is not affected by the new characteristics of short-circuit current caused by the connection of new energy power electronic devices and can be applied to transmission lines of new energy.

    参考文献
    相似文献
    引证文献
引用本文

叶远波,李端超,汪胜和,等.基于广义S变换和皮尔逊相关系数的新能源接入电网纵联保护[J].电力科学与技术学报,2024,39(6):194-202.
YE Yuanbo, LI Duanchao, WANG Shenghe, et al. Pilot protection for new energy access to power grid based on generalized S transform and Pearson correlation coefficient[J]. Journal of Electric Power Science and Technology,2024,39(6):194-202.

复制
分享
文章指标
  • 点击次数:
  • 下载次数:
  • HTML阅读次数:
  • 引用次数:
历史
  • 在线发布日期: 2025-02-14
文章二维码