基于相电流增量的故障区间定位新方法
CSTR:
作者:
通讯作者:

宗伟林(1963),男,副教授,主要从事电力自动化、矿山自动化、工业检测与自动化装置等研究;Email:cumtzwl@126.com

中图分类号:

TM771

基金项目:

江苏省研究生科研与实践创新计划项目(SJCX17_0527,SJCX18_0664);国家级大学生创新训练计划资助(201610290026)


Novel method of fault section location based on phase current increment
Author:
  • 摘要
  • | |
  • 访问统计
  • |
  • 参考文献 [14]
  • | | | |
  • 文章评论
    摘要:

    为解决配电网单相接地故障时定位效果不佳的问题,根据故障发生后健全线路及故障线路故障点下游暂态三相电流增量波形相似,而故障线路故障点上游故障相与非故障相暂态相电流增量波形差异较大的特点,提出一种基于相电流增量的故障区间定位新方法。该方法利用各个检测点的三相电流增量求出各自的功率系数并发送到主机,通过对比相邻检测点的功率系数判断出故障区间。其优势在于仅利用电流作为故障区间定位特征量的同时减少了通信系统的压力。通过仿真和数据分析表明,该方法在各种初始电压相位下发生高、中、低阻接地时均能正确的判断出故障区间,具有原理简单、适用性好的特点。

    Abstract:

    In order to solve the unsatisfactory section location problem of single phase grounding fault in distribution network, a novel method of fault section location based on phase current increment is presented according to the similarities between features of threephase phase current increment waveform in healthy lines and the fault line after the fault point, as well as great difference between healthy lines and the fault line before the fault point. In the method, the power coefficients of each detection point can be calculated by threephase current increment and sent back to host. The fault section is predicted by comparison with the power coefficients of its adjacent detection points. The advantage of this method is that it reduces the pressure of the communication system while only using current as the fault section location characteristic. Furthermore, simulation and data analysis indicate that this method can correctly predict fault section in high, medium and low resistance grounding under every kind of initial angles. It has good applicability under simple theory.

    参考文献
    [1] 束洪春.配电网络故障选线[M].北京:机械工业出版社,2008.
    [2] DL/T 836—2012,供电系统用户供电可靠性评价规定[S].
    [3] DL/T 814—2013,配电自动化系统功能规范[S].
    [4] 李冬梅,胡扬宇,王利利,等.基于改进注入法的直流配电网双端测距故障定位方法[J].智慧电力,2019,47(12):110116.LI Dongmei,HU Yangyu,WANG Lili,et al.Doubleend distance measurement fault location method for DC distribution network based on improved injection method[J].Smart Power,2019,47(12):110116.
    [5] 高志鹏,张慧芬,孙旭娜.注入半波直流的小电流接地故障选线定位方法[J].电力系统保护与控制,2013,41(13):139145.GAO Zhipeng,ZHANG Huifen,SUN Xuna.A method of fault line selection and fault point location with half wave DC injection in distribution network[J].Power System Protection and Control,2013,41(13):139145.
    [6] 曾祥君,尹项根,张哲,等.零序导纳法馈线接地保护的研究[J].中国电机工程学报,2001,21(4):510.ZENG Xiangjun,YIN Xianggen,ZHANG Zhe,et al.Study on feeder grounding fault protection based on zero sequence admittance[J].Proceedings of the CSEE,2001,21(4):510.
    [7] 朱涛.基于SCADA系统的小电流接地故障选线方法研究[J].电力系统保护与控制,2019,47(13):141147.ZHU Tao.Fault line selecting method in nonsolidlyearthed network based on SCADA system[J].Power System Protection and Control,2019,47(13):141147.
    [8] 李斌,束洪春.谐振接地系统单相接地故障瞬时功率分析[J].电网技术,2012,36(7):260268.LI Bin,SHU Hongchun.Analysis on instantaneous power during singlephase earth fault occurred in resonant grounded system[J].Power System Technology,2012,36(7):260268.
    [9] 杨新伟,郭彩霞.基于主频零序功率的配电网故障选线新方法[J].河南师范大学学报:自然科学版,2016,44(5):3337.YANG Xinwei,GUO Caixia.A new method of fault line selection for distribution on network based on zero sequence power of the main frequency[J].Journal of Henan Normal University:Natural Science Edition,2016,44(5):3337.
    [10] 黄宇浩,陈豪威,周佳铭,等.基于暂态零序电流频谱灰关联分析的谐振接地系统故障选线方法[J].电力科学与技术学报,2017,32(3):6974.HUANG Yuhao,CHEN Haowei,ZHOU Jiaming,et al.Faulty feeder detection using grey relation analysis of transient zerosequence current spectrum in resonant grounding system[J].Journal of Electric Power Science and Technology,2017,32(3):6974.
    [11] 李雪云,刘青,李丽英.基于单端行波法的配电网混合线路波头组合式故障测距方法[J].华北电力大学学报:自然科学版,2014,41(5):5561.LI Xueyun,LIU Qing,LI Yingli.Based on singleended traveling wave a head combined fault location method about distribution network the hybrid[J].Journal of North China Electric Power University:Natural Science Edition,2014,41(5):5561.
    [12] 梁睿,靳征,刘建华.基于故障特征频率的单端行波测距新方法[J].电力系统保护与控制,2013,41(15):713.LIANG Rui,JIN Zheng,LIU Jianhua.A new singleended traveling waves fault location method based on characteristic frequency[J].Power System Protection and Control,2013,41(15):713.
    [13] 张帆,潘贞存,张慧芬,等.基于零序电流暂态极大值的小电流接地选线新判据[J].电力系统自动化,2006,30(4):4548.ZHANG Fan,PAN Zhencun,ZHANG Huifen,et al.New criterion of fault line selection in nonsolidly earthed network based on the maximum of zero sequence transient current[J].Automation of Electric Power Systems,2006,30(4):4548.
    [14] 薛永端,徐丙垠,李天友,等.配网自动化系统小电流接地故障暂态定位技术[J].电力自动化设备,2013,33(12):2732.XUE Yongduan,XU Bingyin,LI Tianyou,et al.small current grounding fault location based on transient signals of distribution automation system[J].Electric Power Automation Equipment,2013,33(12):2732.
    相似文献
    引证文献
    网友评论
    网友评论
    分享到微博
    发 布
引用本文

宗伟林,邹 运,戴经纬,等.基于相电流增量的故障区间定位新方法[J].电力科学与技术学报,2020,35(2):128-134.
ZONG Weilin, ZOU Yun, DAI Jingwei, et al. Novel method of fault section location based on phase current increment[J]. Journal of Electric Power Science and Technology,2020,35(2):128-134.

复制
分享
文章指标
  • 点击次数:345
  • 下载次数: 0
  • HTML阅读次数: 0
  • 引用次数: 0
历史
  • 在线发布日期: 2020-09-03
文章二维码