    摘要:

    在配电网中性点经消弧线圈串联阻尼电阻接地方式下现有对地参数测量方法测量误差较大,因此,提出一种改进的配电网对地参数谐振测量方法。该文分析消弧线圈串联阻尼电阻方式下现有对地参数测量方法的局限性,并通过分别构建消弧线圈串联、并联阻尼电阻2种接地方式下的谐振测量等效回路,推导了2种接地方式下配电网对地电容和对地泄漏电导数学表达式。通过在中性点接入变频恒流信号源,向配电网注入特征电流信号并实时测量零序电压互感器开口三角形处特征电压信号,可测得系统谐振频率;进而依据对地参数表达式实现配电网对地参数的快速、准确测量。PSCAD/EMTDC仿真分析和模拟实验验证了所提方法的正确性,仿真分析与实验结果均表明该方法测量对地参数精度高、适用范围广。

    Abstract:

    In the distribution power system with its neutral point grounded by an arc suppression coil connected with the damping resistance in series, the existing method for the grounded parameter measurement is not accurate enough. Therefore, an improved resonance measurement method of grounded parameters is proposed for distribution power systems. In this paper, the influence from the damping resistance on the arcsuppression coil compensation is analyzed. And then, the equivalent circuit of resonance measurement is constructed respectively for two grounding modes whose arc suppression coils connect a damping resistance in series and parallel. In addition, the mathematical expressions of the distribution power system's grounded capacitance and grounded leakage conductance are derived respectively. A current signal with characteristic frequency is directly injected into the distribution network through the neutral point connected to the constant current signal source with the variable frequency, and the characteristic voltage signal is measured through the triangular side of zerosequence voltage transformer. In terms of the grounded parameter expressions, the fast and accurate grounded parameter measurement in distribution power system is realized by exploring the system resonance frequency. The correctness of proposed method is verified by PSCAD/EMTDC simulation. It is shown that this method has the high precision and wide application.

    参考文献
    [1] 要焕年,曹梅月.电力系统谐振接地(第二版)[M].北京:中国电力出版社,2009.
    [2] GBT 50064—2014,交流电气装置的过电压保护和绝缘配合设计规范[S].
    [3] 杨锐,姜铁卫,夏磊.应用于配电网谐振接地系统的阻尼电阻研究[J].陕西电力,2015,43(2):6467.YANG Rui,JIANG Tiewei,XIA Lei.Application research of damping resistance in resonant grounded system for distribution network[J].Shaanxi Electric Power,2015,43(2):6467.
    [4] 滕昊.带阻尼电阻的谐振接地系统电容电流精确测量方法[J].电力科学与技术学报,2017,32(1):97102.TENG Hao.Accurate measurement method of capacitive current in resonant grounding system with damping resistance[J].Journal of Electric Power Science and Technology,2017,32(1):97102.
    [5] 靳汪一,曾祥君,伍智华,等.基于IGBT新型消弧线圈自动调谐系统[J].电力科学与技术学报,2010,25(2):5660.JIN Wangyi,ZENG Xiangjun,WU Zhihua,et al.A novel IGBT based arcsuppression coil automatic tuning system[J].Journal of Electric Power Science and Technology,2010,25(2):5660.
    [6] 彭沙沙,曾祥君,喻琨,等.基于二次注入的配电网接地故障有源电压消弧方法[J].电力系统保护与控制,2018,46(20):142149.PENG Shasha,ZENG Xiangjun,YU Kun,et al.Active arcsuppression method of grounding fault for distribution network based on secondary injection[J].Power System Protection and Control,2018,46(20):142149.
    [7] 刘宝稳,马宏忠,沈培锋,等.新型接地故障基波电流全补偿柔性控制系统[J].中国电机工程学报,2016,36(9):23222330.LIU Baowen,MA Hongzhong,SHEN Peifeng,et al.New Flexible Control System of Full Compensation Singlephase Ground Fault Fundamental Current[J].Proceedings of the CSEE,2016,36(9):23222330.
    [8] 杨磊,曾祥君,喻锟,等.新型谐振接地系统接地故障全补偿方法[J].电力自动化设备,2018,38(11):5762.YANG Lei,ZENG Xiangjun,YU Kun,et al.Novel method of full compensation for grounding fault of resonant grounding system[J].Electric Power Automation Equipment,2018,38(11):5762.
    [9] 李玲玲,孙鹤旭,王晓宏.谐振接地电力网自动调谐的新方法[J].中国电机工程学报,2003,23(6):7780.LI Lingling,SUN Hexu,WANG Xiaohong.A new automatic tuning method for resonance grounding power network[J].Proceedings of the CSEE,2003,23(6):7780.
    [10] 李明贤,解洪光,张喜玲,等.基于谐波分量的配电网分相对地参数辨识新方法[J].智慧电力,2019,47(4):9398.LI Mingxian,XIE Hongguang,ZHANG Xiling,et al.A new method for relative parameter identification of dstribution network based on harmonic component[J].Smart Power,2019,47(4):9398.
    [11] 闫腾飞,李康,李晓波,等.基于牛顿拉夫逊法的配电网电容电流测量新方法[J].电力系统保护与控制,2017,45(7):15.YAN Tengfei,LI Kang,LI Xiaobo,et al.A new capacitive current measurement method of distribution network based on NewtonRaphson method[J].Power System Protection and Control,2017,45(7):15.
    [12] 贺良华,葛来,孙宝金.基于谐振频率预测模型的配电网电容电流测量方法[J].电力系统自动化,2018,42(2):143147+159.HE Lianghua,GE Lai,SUN Baojin.Capacitive Current Measuring Method for Distribution Networks Based on Resonant Frequency Prediction Model[J].Automation of Electric Power Systems,2018,42(2):143147+159.
    [13] 刘力,孙结中.一种测量配电网电容电流的新方法[J].电网技术,2001,25(5):6365.LIU Li,SUN Jiezhong.A new method to measure the capacitance current of distribution network[J].Power System Technology,2001,25(5):6365.
    [14] 黎新吉,张平,陈博,等.中性点不接地配电网电容电流在线测量方法比较[J].电力科学与技术学报,2008,23(2):6671.LI Xinji,ZHANG Ping,CHEN Bo,et al.Capacitive current online measurement methods comparing for unearthed distribution systems[J].Journal of Electric Power Science and Technology,2008,23(2):6671.
    [15] 曾祥君,尹项根,于永源,等.基于注入变频信号法的经消弧线圈接地系统控制与保护新方法[J].中国电机工程学报,2000,20(1):3033+37.ZENG Xiangjun,YIN Xianggen,YU Yongyuan,et al.New methods for control and protection relay in a compensated medium voltage distribution network based on injecting various frequency current[J].Proceedings of the CSEE,2000,20(1):3033+37.
    [16] 宋晓燕,孙岩洲,宋紫嫣,等.基于零序PT二次侧注入信号的配电网电容电流测量新方法[J].电力系统保护与控制,2014,42(19):134138.SONG Xiaoyan,SUN Yanzhou,SONG Ziyan et al.A new method of distribution network capacitive current measurement based on injecting signals into the secondary side of the zero sequence PT[J].Power System Protection and Control,2014,42(19):134138.
    [17] 靳维,袁朋生,张洋,等.基于调整中性点接地阻抗的配电网电容电流测量方法[J].电力系统保护与控制,2015,43(7):3741.JIN Wei,YUAN Pengsheng,ZHANG Yang,et al.A method of measuring capacitive current in distribution network based on adjusting the neutral grounding impedance[J].Power System Protection and Control,2015,43(7):3741.
    [18] 朱珂,殷鹏,刘颖英,等.利用电力电子扰动技术的系统对地电容检测方法[J].电力系统自动化,2016,40(23):150156.ZHU Ke,YIN Peng,LIU Yingying,et al.Detection method for system grounding capacitance using power electronic disturbance technology[J].Automation of Electric Power Systems,2016,40(23):150156.
    [19] 杨帆.基于有源工频电流注入的配电网对地参数精确测量[J].电力科学与技术学报,2018,33(1):8187.YANG Fan.Ground parameters accuracy measurement in distribution network based on active current injection with power frequency[J].Journal of Electric Power Science and Technology,2018,33(1):8187.
    [20] Zeng X J,Xu Y,Wang Y Y.Some novel techniques for insulation parameters measurement and Petersencoil control in distribution systems[J].IEEE Transactions on Industrial Electronics,2010,57(4):14451451.
    相似文献
    引证文献
引用本文

曾祥君,刘玉玲,喻 锟.改进的配电网对地参数谐振测量方法[J].电力科学与技术学报,2020,35(3):3-11.
ZENG Xiangjun, LIU Yuling, YU Kun. An improved resonance measurement method of grounded parameters for distribution networks[J]. Journal of Electric Power Science and Technology,2020,35(3):3-11.

复制
分享
文章指标
  • 点击次数:245
  • 下载次数: 0
  • HTML阅读次数: 0
  • 引用次数: 0
历史
  • 在线发布日期: 2020-09-14
文章二维码