配网绝缘渐损接地增量电流波形及选线定位分析
CSTR:
作者:
通讯作者:

周奕轩(1992),女,硕士研究生,主要从事智能配电网、传感技术和能源检测等研究;Email:15618228061@163.com

中图分类号:

TH411

基金项目:

上海市电站自动化技术重点实验室资助(13DZ2273800);国家级大学生创新训练计划资助(201610290026);江苏省研究生科研与实践创新计划项目(SJCX17_0527)


Incremental current waveform analysis and lineselection faultlocation method for intermittent breakdown grounding in distribution network
Author:
  • 摘要
  • | |
  • 访问统计
  • |
  • 参考文献 [10]
  • | | | |
  • 文章评论
    摘要:

    为提高配网包括绝缘渐损接地在内的单相接地选线定位的可靠性,仿真观察绝缘渐损接地在不同阶段的电流波形。首先,根据这些电流波形及发展变化的共有规律,选择接地相的次暂态锯齿波增量电流和健全相与之对应时刻的增量电流作为配网绝缘渐损接地自举选线定位的判据信号源,分析锯齿波电流反映所有接地电流的通用性特点,并研究设计锯齿波标量和矢量相位差的计算方法;然后,仿真研究并比较包括锯齿波在内的单相接地电流与操作性、诱发性扰动电流的波形特征,为辨识真伪单相接地找寻判别基准,并以此为依据,研究设计包括绝缘渐损在内的配网单相接地防误辨识和选线定位方法;最后,采用所制作的接地定位器在低压配网模型的合环运行线路上验证所设计方法的正确性。

    Abstract:

    In order to improve the reliability of lineselection and faultlocation for singlephase grounding failures in distribution network, the current waveform at different stages were studied and stimulated. Firstly, in terms of the summarized common features of current waveforms during their development, the incremental current of the subtransient sawtooth wave in the grounding phase and the incremental current in the sound phase are selected as the criterion signal sources for the fault location of the insulation loss in distribution networks. The general characteristics of all grounding currents reflected by the saw tooth currents are analyzed. Then, the difference of waveform characteristics is analyzed between singlephase grounding current and operationinduced disturbance currents. It provides a criterion for identifying the authenticity of singlephase grounding failure. The line selection and location method are proposed for the singlephase grounding including the insulation loss to avoid misidentification. Finally, the proposed method is applied to the grounding locator in a low voltage distribution network model for verification.

    参考文献
    [1] 贺家李.电力系统继电保护原理[M].北京:中国电力出版社,2010.
    [2] 王家林,夏立,吴正国,等.电力系统微机保护故障信息检测算法综述[J].电测与仪表,2011,48(2):15+35.WANG Jialin,XIA Li,WU Zhengguo,et al.State of arts of fault detection arithmetic of power systems microcomputer protection[J].Electrical Measurement & Instrumentation,2011,48(2):15+35.
    [3] 李卫国,许文文,乔振宇,等.基于暂态零序电流凹凸特征的配电网故障区段定位方法[J].电力系统保护与控制,2020,48(10):164173.LI Weiguo,XU Wenwen,QIAO Zhenyu,et al.Fault section location method for a distribution network based on concave and convex characteristics of transient zero sequence current[J].Power System Protection and Control,2020,48(10):164173.
    [4] 但扬清,赵伟,朱艳伟,等.基于ABCDNN的小电流接地故障选线方法[J].智慧电力,2019,47(4):4652.DAN Yangqing,ZHAO Wei,ZHU Yanwei,et al.Fault line selection in small current ground power system based on ABCDNN[J].Smart Power,2019,47(4):4652.
    [5] 梁睿,杨学君,薛雪,等.零序分布参数的单相接地故障精确定位研究[J].电工技术学报,2015,30(12):472479.LIANG Rui,YANG Xuejun,XUE Xue,et al..Study of accurate singlephase grounding fault location based on distributed parameter theory using data of zero sequence components[J].Transactions of China Electrotechnical Society,2015,30(12):472479.
    [6] 宋国兵,李广,于叶云,等.基于相电流突变量的配电网单相接地故障区段定位[J].电力系统自动化,2011,35(21):8490.SONG Guobing,LI Guang,YU Yeyun,et al.Singlephase earth fault section location based on phase current fault component in distribution network[J].Automation of Electric Power Systems,2011,35(21):8490.
    [7] 吴乐鹏,黄纯,林达斌,等.基于暂态小波能量的小电流接地故障选线新方法[J].电力自动化设备,2013,33(5):7075.WU Lepeng,HUANG Chun,LIN Dabin,et al.Faulty line selection based on transient wavelet energy for nonsolidearthed network[J].Electric Power Automation Equipment,2013,33(5):7075.
    [8] 李振兴,吴李群,谭洪,等.基于简单通信的双端行波测距新方法[J].中国电力,2018,51(3):7479.LI Zhenxing,WU Liqun,TAN Hong,et al.A novel method for double terminal traveling wave fault location based on simple communication[J].Electric Power,2018,51(3):7479.
    [9] 付华,刘公权,邢亮.基于同步挤压小波变换的故障行波测距方法[J].电力系统保护与控制,2020,48(2):1824.FU Hua,LIU Gongquan,XING Liang.Fault traveling wave ranging method based on synchrosqueezing wavelet transform[J].Power System Protection and Control,2020,48(2):1824.
    [10] 孙永超,邰能灵,郑晓冬.含分布式电源的配电网单相接地故障区段定位新方法[J].电力科学与技术学报,2016,31(3):7380.SUNYongchao,TAI Nengling,ZHENG Xiaodong.Research on singlephase grounding fault location of distribution network with DG[J].Journal of Electric Power Science and Technology,2016,31(3):7380.
    相似文献
    引证文献
    网友评论
    网友评论
    分享到微博
    发 布
引用本文

周奕轩,皮 杰,宋天宝,等.配网绝缘渐损接地增量电流波形及选线定位分析[J].电力科学与技术学报,2020,35(4):58-65.
ZHOU Yixuan, PI Jie, SONG Tianbao, et al. Incremental current waveform analysis and lineselection faultlocation method for intermittent breakdown grounding in distribution network[J]. Journal of Electric Power Science and Technology,2020,35(4):58-65.

复制
分享
文章指标
  • 点击次数:442
  • 下载次数: 2881
  • HTML阅读次数: 0
  • 引用次数: 0
历史
  • 在线发布日期: 2020-09-04
文章二维码