配电线路零序过流保护涌流误动风险评估及借助5G的应对策略研究
CSTR:
作者:
中图分类号:

TM740

基金项目:

中国南方电网有限责任公司科技项目(0000002020030103XT00046)


Assessment of distribution line zero-sequence overcurrent protection inrush maloperation risk and corresponding countermeasure with 5G
Author:
  • 摘要
  • | |
  • 访问统计
  • |
  • 参考文献 [19]
  • | | | |
  • 文章评论
    摘要:

    高压内置型高阻抗变压器空载合闸中会产生幅值较高的零序涌流,其可能会经相邻变压器渗透至经小电阻接地的20 kV配电网络中,引发配网线路零序过流保护误动,进而导致用户失电。针对这一问题,首先结合零序涌流的半解析表达式,对高压内置型高阻抗变压器的零序涌流幅值特征进行量化分析;然后依托PSCAD/EMTDC平台验证了模型的有效性和保护误动的可能性;最后基于Matlab编写配网线路零序过流保护的误动风险评估程序,结合变压器和保护的实际参数,量化高压内置型高阻抗变压器空载合闸工况下相邻配网线路零序过流保护的误动概率。计算结果明确零序过流保护在高压内置型高阻抗变压器空载合闸期间的动作情况,在此基础上,提出一种借助5G通信技术的零序过流保护涌流闭锁策略,并分析该策略的可行性。

    Abstract:

    The high zero-sequence inrush will be caused when the high-voltage built-in high-impedance transformer performs no-load closing, which may penetrate into the 20 kV distribution network with a grounding small resistance through the adjacent transformers, leading to the maloperation of zero-sequence overcurrent protection of distribution lines. This will result in the power loss of users. To solve this, the amplitude characteristics of high-voltage built-in high-impedance transformers are analyzed based on zero-sequence inrush formula. Then, the validity of the model and the possibility of protection maloperation are studied based on PSCAD/EMTDC simulation platform. At last, the calculation procedure for assessing risks of zero-sequence over-current protection in distribution networks is produced by MATLAB, where the actual parameter is used to quantitatively analyze the maloperation probability of zero-sequence overcurrent protection when a high-voltage built-in high-impedance transformer performs no-load energize. The experienmental results indicate protection operation situations. A protection blocking strategy based on 5G wireless communication technology is proposed and its feasibility is analyzed.

    参考文献
    [1] 李晓华,罗龙波,谢金泉,等.高压内置型高阻抗变压器涌流特性对保护的影响[J].电力系统自动化,2016,40(11):108-114.LI Xiaohua,LUO Longbo,XIE Jinquan,et al.Impact of inrush current characteristics of high-voltage built-in high-impedance transformer on relay[J].Automation of Electric Power Systems,2016,40(11):108-114.
    [2] 李甜甜.20 kV配电网中性点接地方式与继电保护改造的研究[D].北京:北京交通大学,2010.
    [3] 张章,胡源,罗涛,等.中压直流配电系统保护技术研究综述[J].电测与仪表,2020,57(23):109-118.ZHANG Zhang,HU Yuan,LUO Tao,et al.Review on research of protection technology for medium voltage DC distribution system[J].Electrical Measurement & Instrumentation,2020,57(23):109-118.
    [4] 任华,李健,弥潇,等.±1 100 kV吉泉线雷击致灾因子权重分析及高风险杆塔筛选[J].中国电力,2022,55(2):115-124.REN Hua,LI Jian,MI Xiao,et al.Analysis of lightning disaster factors and high risk tower identification for ±1 100 kV Jiquan line[J].Electric Power,2022,55(2):115-124.
    [5] 计丽妍,李存斌,贾雪枫,等.多证据融合下电力信息物理系统风险评估研究[J].智慧电力,2021,49(10):23-29.JI Liyan,LI Cunbin,JIA Xuefeng,et al.Risk assessment of cyber-physical power system based on multi-evidence fusion[J].Smart Power,2021,49(10):23-29.
    [6] 摆世彬,田志浩,刘刚,等.高压内置型变压器备自投引发线路零序过流保护误动的风险分析[J].变压器,2021,58(1):23-29+67.BAI Shibin,TIAN Zhihao,LIU Gang,et al.The risk analysis of zero sequence overcurrent protection maloperation caused by automatic device transfer of transformer[J].Transformer,2021,58(1):23-29+67.
    [7] 陈蕾,咸日常,郑春旭,等.系统单相接地故障下接地变压器的运行特性分析[J].电力系统保护与控制,2021,49(12):56-64.CHEN Lei,XIAN Richang,ZHENG Chunxu,et al.Analysis of the operational characteristics of a grounding transformer when there is a single-phase grounding fault of the system[J].Power System Protection and Control,2021,49(12):56-64.
    [8] 张员宁,黄景光,张艳华,等.利用双重特征量鉴别变压器励磁涌流的高阶统计原理[J].电力系统保护与控制,2021,49(24):21-30.ZHANG Yuanning,HUANG Jingguang,ZHANG Yanhua,et al.High order statistical theory for identifying transformer inrush current by using dual characteristics[J].Power System Protection and Control,2021,49(24):21-30.
    [9] 孙直,孟润泉,韩肖清.微电网与配电网间串联变压器磁饱和抑制策略研究[J].电网与清洁能源,2021,37(6):29-34.SUN Zhi,MENG Runquan,HAN Xiaoqing.Research on magnetic saturation suppression strategy of series transformers between microgrid and distribution network[J].Power System and Clean Energy,2021,37(6):29-34.
    [10] 王育学,曹文斌,黄明辉,等.变压器零模涌流解析分析及其等值电路[J].电网技术,2018,42(12):3960-3968.WANG Yuxue,CAO Wenbin,HUANG Minghui,et al.Mathematical analysis for zero-mode inrush current of transformer and its equivalent circuit[J].Power System Technology,2018,42(12):3960-3968.
    [11] 宋志伟,徐舒,王润路,等.5G通信条件下的线路差动保护优化策略研究[J].供用电,2021,38(5):17-22.SONG Zhiwei,XU Shu,WANG Runlu,et al.Research on optimization strategy of line differential protection under 5G communication conditions[J].Distribution & Utilization,2021,38(5):17-22.
    [12] 张宁,杨经纬,王毅,等.面向泛在电力物联网的5G通信:技术原理与典型应用[J].中国电机工程学报,2019,39(14):4015-4025.ZHANG Ning,YANG Jingwei,WANG Yi,et al.5G communication for the ubiquitous internet of things in electricity:technical principles and typical applications[J].Proceedings of the CSEE,2019,39(14):4015-4025.
    [13] 胡光宇,刘龙,刘文贵,等.5G在电力系统中的建设方案研究[J].电力信息与通信技术,2020,18(8):73-79.HU Guangyu,LIU Long,LIU Wengui,et al.A study on 5G construction scheme in electric power system[J].Electric Power Information and Communication Technology,2020,18(8):73-79.
    [14] 黄建伟.5G移动通信发展趋势与相关关键技术研究[J].通讯世界,2019,26(8):116-117.HUANG Jianwei.Research on the development trend and related key technologies of 5G mobile communica-tion[J].Telecom World,2019,26(8):116-117.
    [15] 尤肖虎,潘志文,高西奇,等.5G移动通信发展趋势与若干关键技术[J].中国科学:信息科学,2014,44(5):551-563.YOU Xiaohu,PAN Zhiwen,GAO Xiqi,et al.5G mobile communication development trend and several key technologies[J].Science in China:Information Science,2014,44(5):551-563.
    [16] 马云龙,李秀广,周秀,等.基于高压真空快速断路器的变压器励磁涌流抑制技术研究[J].高压电器,2022,58(10):136-142.MA Yunlong,LI Xiuguang,ZHOU Xiu,et al.Research on excitation inrush current suppression technology of transformer based on high voltage vacuum fast circuit breaker[J].High Voltage Apparatus,2022,58(10):136-142.
    [17] 张保会,尹项根.电力系统继电保护(第二版)[M].北京:中国电力出版社,2010:56-57.
    [18] SHAFI M,MOLISCH A F,SMITH P J,et al.5G:a tutorial overview of standards,trials,challenges,deployment,and practice[J].IEEE Journal on Selected Areas in Communications,2017,35(6):1201-1221.
    [19] 徐江涛,姜海波,刘洋,等.电力物联网D2D通信中模式预选的多播重传技术[J].电力科学与技术学报,2021,36(4):196-202.XU Jiangtao,JIANG Haibo,LIU Yang,et al.A multicast retransmission scheme based on the pre-selected mode for D2D communications of electric internet of things networks[J].Journal of Electric Power Science and Technology,2021,36(4):196-202.
    相似文献
    引证文献
    网友评论
    网友评论
    分享到微博
    发 布
引用本文

彭业,金震,陈宏山,等.配电线路零序过流保护涌流误动风险评估及借助5G的应对策略研究[J].电力科学与技术学报,2022,37(5):100-108.
Peng Ye, Jin Zhen, Chen Hongshan, et al. Assessment of distribution line zero-sequence overcurrent protection inrush maloperation risk and corresponding countermeasure with 5G[J]. Journal of Electric Power Science and Technology,2022,37(5):100-108.

复制
分享
文章指标
  • 点击次数:177
  • 下载次数: 786
  • HTML阅读次数: 0
  • 引用次数: 0
历史
  • 在线发布日期: 2022-12-01
文章二维码