计及时变转移速率与计划检修的继电保护设备动作预测方法
CSTR:
作者:
中图分类号:

TM774

基金项目:

2019年内蒙古自治区科技攻关项目(2019GG373)


Action prediction model of relay protection devices considering the time-varying transfer rate and planned maintenance
Author:
  • 摘要
  • | |
  • 访问统计
  • |
  • 参考文献 [20]
  • | | | |
  • 文章评论
    摘要:

    目前在继电保护设备动作行为预测中,利用状态转移模型进行状态分类与概率预测时,设备老化、计划检修因素对预测模型影响的描述不够准确,难以对继电保护设备的未来动作情况进行准确反映。本文基于表征设备老化及检修的改进三参数Weibull分布,利用鲸鱼算法求解更为准确的改进三参数Weibull分布函数,构建了具有时变转移速率的连续时间Markov链状态转移模型,并利用计划检修节点表征保护设备的役龄回退,利用状态观测节点简化转移概率计算,进而基于Markov状态转移模型提出了计及时变转移速率与计划检修的动作行为预测方法。基于保护实例数据计算拟合了Weibull曲线,通过仿真对比实验对预测结果进行综合分析,验证了状态转移模型及预测方法的合理性。

    Abstract:

    At present, in the behavior prediction of relay protection equipment, the state transition model is used for state classification and probability prediction. The description of the influence of equipment aging and planned maintenance factors on the prediction model is not accurate enough, and it is thus difficult to accurately reflect the future behavior of the relay protection equipment. Based on the improved three-parameter Weibull distribution that characterizes equipment aging and maintenance, this paper uses the whale algorithm to further enhance the three-parameter Weibull distribution function, constructs a continuous Markov chain state transition model with a time-varying transition rate. In this model, planned maintenance nodes are used to characterize the service age regression of the protection equipment, the state observation node to simplify the calculation of the transition probability, and then an action behavior prediction algorithm that calculates the time-varying transition rate and planned maintenance can be proposed. The Weibull curve is calculated and fitted based on the case database, and the predicted actions are comprehensively analyzed through the simulated comparison experiments, which verifies the rationality of the state transition model and the prediction algorithm.

    参考文献
    [1] 韩悌,柯贤波,霍超,等.多直流、高占比新能源电力系统应对严重扰动新技术研究[J].智慧电力,2020,48(4):9-12+27.HAN Ti,KE Xianbo,HUO Chao,et al.New technology coping with serious disturbance in power system with multiple DC and high ratio new energy[J].Smart Power,2020,48(4):9-12+27.
    [2] 皇甫成,邱婷,梁吉,等.一种考虑电力系统频率安全的新能源并网限值评估方法[J].电网与清洁能源,2021,37(2):85-90+98.HUANGFU Cheng,QIU Ting,LIANG Ji,et al.A sustainable energy penetration limit evaluation method considering power system frequency security[J].Power System and Clean Energy,2021,37(2):85-90+98.
    [3] 肖友强,邓步青,文云峰.计及送端电网频率稳定的直流联络线极限承载能力评估[J].电力科学与技术学报,2021,36(2):3-12.XIAO Youqiang,DENG Buqing,WEN Yunfeng.Total transfer capability assessment of HVDC tie-lines based on frequency stability of the sending-end grid[J].Journal of Electric Power Science and Technology,2021,36(2):3-12.
    [4] 吴旭,张建华,吴林伟,等.输电系统连锁故障的运行风险评估算法[J].中国电机工程学报,2012,32(34):74-82+12.WU Xu,ZHANG Jianhua,WU Linwei,et al.Method of operational risk assessment on transmission system cascading failure[J].Proceedings of the CSEE,2012,32(34):74-82+12.
    [5] 李碧君,董希建,颜云松,等.基于控制功效受损模式的大型稳控系统可靠性评估[J].中国电力,2020,53(5):32-38.LI Bijun,DONG Xijian,YAN Yunsong,et al.Reliability assessment of large scale security and stability control system based on control efficacy reduction mode[J].Electric Power,2020,53(5):32-38.
    [6] 刘琨,黄明辉,李一泉,等.智能变电站继电保护在线运检方法研究[J].电力系统保护与控制,2020,48(7):58-65.LIU Kun,HUANG Minghui,LI Yiquan,et al.Research on online operation method for protective relay of smart substation[J].Power System Protection and Control,2020,48(7):58-65.
    [7] 叶远波,刘宏君,黄太贵,等.变电站继电保护设备状态检修可靠性分析方法研究[J].电力系统保护与控制,2021,49(10):170-177.YE Yuanbo,LIU Hongjun,HUANG Taigui,et al.Research on the reliability analysis method of condition-based maintenance of relay protectionequipment in sub-station[J].Power System Protection and Control,2021,49(10):170-177.
    [8] 李浩,林湘宁,喻锟,等.基于连续时间马尔可夫链的继电保护装置动作行为预测模型[J].中国电机工程学报,2018,38(S1):121-128.LI Hao,LIN Xiangning,YU Kun,et al.Based on continuous timeMarkov chain prediction model of action behavior of relay protection device[J].Proceedings of the CSEE,2018,38(S1):121-128.
    [9] XU X,MITRA J,WANG T,et al.An evaluation strategy for microgrid reliability considering the effects of protection system[J].IEEE Transactions on Power Delivery,2015,31(5):434-450.
    [10] DAI Z,WANG Z,JIAO Y.Bayes Monte-Carlo assessment method of protection systems reliability based on small failure sample data[J].IEEE Transactions on Power Delivery,2014,29(4):1841-1848.
    [11] PAUL D,CHAVDARIAN P B R.Undercurrent protection power system:a novel ground-fault protection relay scheme[J].IEEE Industry Applications Magazine,2015,21(1):23-32.
    [12] 徐岩,白静,戴志辉,等.一种基于威布尔分布的继电保护装置可靠性分析的新方法[J].华北电力大学学报(自然科学版),2012,39(4):15-19.XU Yan,BAI Jing,DAI Zhihui,et al.A new method for protective relay reliability analysis based on Weibull distribution[J].Journal of North China Electric Power University(Natural Science Edition),2012,39(4):15-19.
    [13] 王嘉琦,徐岩,彭雅楠,等.基于灰色—三参数威布尔分布模型的继电保护装置可靠性参数估计[J].电网技术,2019,43(4):1354-1360.WANG Jiaqi,XU Yan,PENG Yanan,et al.Estimation of reliability parameters of protective relays based on grey-three-parameter Weibull distribution model[J].Power System Technology,2019,43(4):1354-1360.
    [14] 张焕青,雷鸣,严利雄,等.面向智能变电站继电保护可靠性评估方法研究[J].电测与仪表,2020,57(14):57-62.ZHANG Huanqing,LEI Ming,YAN Lixiong,et al.Research on reliability evaluation method of relay protection for smart substation[J].Electrical Measurement& Instrumentation,2020,57(14):57-62.
    [15] 何旭,姜宪国,张沛超,等.基于SVM的小样本条件下继电保护可靠性参数估计[J].电网技术,2015,39(5):1432-1437.HE Xu,JIANG Xianguo,ZHANG Peichao,et al.SVM based parameter estimation of relay protection reliability with small samples[J].Power System Technology,2015,39(5):1432-1437.
    [16] 颜云松,孙宁,张楠,等.基于预防检修周期优化的电网稳定控制系统失效风险评估[J].电力系统保护与控制,2021,49(17):139-146.YAN Yunsong,SUN Ning,ZHANG Nan,et al.Evaluation of unavailability risk of the security and stability control system of power systems based on optimization of the preventive maintenance period[J].Power System Protection and Control,2021,49(17):139-146.
    [17] 李生虎,赵慧洁,周慧敏,等.基于可靠性灵敏度的UHVDC系统预防性检修优化[J].电力系统保护与控制,2022,50(3):68-75.LI Shenghu,ZHAO Huijie,ZHOU Huimin.et al.Reliability sensitivity-based optimization for a UHVDC transmission system with preventive maintenance[J].Power System Protection and Control,2022,50(3):68-75.
    [18] 叶远波,刘宏君,黄太贵,等.变电站继电保护设备状态检修可靠性分析方法研究[J].电力系统保护与控制,2021,49(10):170-177.YE Yuanbo,LIU Hongjun,HUANG Taigui,et al.Research on the reliability analysis method of condition-based maintenance of relay protection equipment in substation[J].Power System Protection and Control,2021,49(10):170-177.
    [19] WANG L J,WANG G,SUN Z B.Determination of the optimum routine maintenance intervals for protective systems[C]//IEEE Power & Energy Society General Meeting,Calgary,Canada:IEEE,2009.
    [20] 丁茂生,王钢,贺文,等.基于可靠性经济分析的继电保护最优检修间隔时间[J].中国电机工程学报,2007,27(25):44-48.DING Maosheng,WANG Gang,HE Wen,et al.The optimum routine maintenance interval of protection based on reliability economic analysis[J].Proceedings of the CSEE,2007,27(25):44-48.
    相似文献
    引证文献
    网友评论
    网友评论
    分享到微博
    发 布
引用本文

陶军,钟鸣,周洋,等.计及时变转移速率与计划检修的继电保护设备动作预测方法[J].电力科学与技术学报,2022,37(5):133-143.
Tao Jun, Zhong Ming, Zhou Yang, et al. Action prediction model of relay protection devices considering the time-varying transfer rate and planned maintenance[J]. Journal of Electric Power Science and Technology,2022,37(5):133-143.

复制
分享
文章指标
  • 点击次数:134
  • 下载次数: 491
  • HTML阅读次数: 0
  • 引用次数: 0
历史
  • 在线发布日期: 2022-12-01
文章二维码