10 kV线路首端负荷安全域边界的估算方法
作者:
作者单位:

(1.长沙理工大学电气与信息工程学院,湖南 长沙 410114;2.国网湖南省电力有限公司株洲供电公司,湖南 株洲 412000)

作者简介:

通讯作者:

竺 炜(1968—) ,男,博士,教授,主要从事电力系统稳定分析与控制研究;E?mail:738660686@qq.com

中图分类号:

TM712

基金项目:

国家自然科学基金(52077009);湖南省教育厅重点项目(20A013);湖南省株洲市供电公司科技项目(SGHNZZ00YYJS1901552)


Estimation method of security region boundary of 10 kV line head end load
Author:
Affiliation:

(1.School of Electrical & Information Engineering, Changsha University of Science & Technology, Changsha 410114, China; 2.Zhuzhou Power Supply Company, State Grid Hunan Electric Power Co., Ltd., Zhuzhou 412000, China)

Fund Project:

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
  • |
  • 文章评论
    摘要:

    10 kV线路的主线具有单端注入的母线功能,其末端容易出现低电压问题。将主线压降约束转变为出线负荷约束,可为安全运行与规划提供极大便利,故提出首端负荷安全域边界的估算方法。首先针对沿线众多的台区负荷,基于分段压降特征,提出主线压降快速估算的力矩法;然后将实际台区负荷分布,等效为沿线均衡分布附加若干重载点的特征形式,更加符合实际情况;最后基于力矩法得到线路首端负荷与压降的关系,进而得到首端负荷安全域边界的线性化方程。算例结果表明,力矩法的压降分析和安全域边界分析都能满足工程精度要求。基于首端负荷安全域边界可得到10 kV线路的承载裕度,便于负荷控制和配网滚动规划,具有较好的工程应用价值。

    Abstract:

    Due to bus bar function of single?ended injection for 10 kV main line, the end?terminal is prone to suffering low voltage problems. Transforming the main line voltage drop constraint into the outlet load constraint can provide great convenience for the safe operation and planning of power grid. Therefore, an estimation method of the first?end load security region boundary is proposed in this paper. Aiming at the numerous station loads along the line, a torque method for rapid estimation of the voltage drop across the main line basing on segmented voltage drop characteristics is proposed. Then the actual station load distribution is equivalent to the characteristic form of balanced distribution along the line with several heavy load points, which is more consistent with the actual situation. Based on the moment method, the relationship between the load at the head end of the line and the voltage drop is obtained, and finally the linearized equation of the safety zone boundary of the head load is obtained. The results of the calculation examples show that the voltage drop analysis and safety zone boundary analysis of the moment method satisfy the engineering accuracy requirements. Based on the boundary of the first?end load safety zone, the load margin of the 10 kV line can be obtained, which is convenient for load controlling and rolling distribution network planning, and has good engineering application value.

    参考文献
    相似文献
    引证文献
引用本文

竺 炜,高 琪,李爱元,等.10 kV线路首端负荷安全域边界的估算方法[J].电力科学与技术学报,2023,38(1):114-121.
ZHU Wei, GAO Qi, LI Aiyuan, et al. Estimation method of security region boundary of 10 kV line head end load[J]. Journal of Electric Power Science and Technology,2023,38(1):114-121.

复制
分享
文章指标
  • 点击次数:
  • 下载次数:
  • HTML阅读次数:
  • 引用次数:
历史
  • 收稿日期:
  • 最后修改日期:
  • 录用日期:
  • 在线发布日期: 2023-04-10
  • 出版日期: