基于CPO‑VMD的输电线路行波故障测距方法
作者:
作者单位:

(东北电力大学电气工程学院,吉林 吉林 132012)

通讯作者:

曲振国(1999—),男,硕士研究生,主要从事输电线路故障诊断、故障定位方面的研究;E?mail:Q13613507015@163.com

中图分类号:

TM75

基金项目:

吉林省科技厅重点科技攻关项目(20170204068GX);国网吉林省电力公司科技项目(SGJLLY00YJJS2300282)


Traveling wave fault location method of transmission line based on CPO‑VMD
Author:
Affiliation:

(School of Electrical Engineering, Northeast Electric Power University, Jilin 132012, China)

  • 摘要
  • | |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • | | |
  • 文章评论
    摘要:

    针对长距离输电线路故障行波波头检测精度较低,故障检测装置时钟不同步和行波波速不确定造成的测距偏差问题,提出一种改进变分模态分解(variational mode decomposition, VMD)联合Teager?Kaiser能量算子(Teager?Kaiser energy operator, TKEO)来检测故障行波波头,结合不依赖对时和波速的双端行波测距公式的输电线路故障测距新方法。先利用冠豪猪优化算法(crested porcupine optimizer, CPO)优化VMD参数;然后,将故障行波的线模和零模分量经VMD分解后,通过TKEO能量算子检测各分量初始波头;最后,根据线模和零模分量初始波头到达测量点的时间差,列写故障距离与差值距离之间的比例关系,得到不依赖对时和波速的双端行波测距公式。利用MATLAB/Simulink搭建220 kV输电线路故障仿真模型,仿真结果表明该测距方法在噪声和不同接地电阻、故障类型下均具有良好的适用性,且测距结果精度较高。

    Abstract:

    To address the low detection accuracy of traveling wave heads for long-distance transmission line faults as well as the location deviation caused by the clock asynchronization of fault detection devices and the uncertainty of traveling wave velocity, this paper proposes a new fault location method for transmission lines based on improved variational mode decomposition (VMD) combined with Teager-Kaiser energy operator (TKEO) to detect the fault traveling wave head and the double-ended traveling wave location formula independent of timing and wave velocity. Firstly, the crested porcupine optimizer (CPO) is used to optimize VMD parameters. Then the line mode and zero mode components of the fault traveling wave are decomposed by VMD, and the initial wave heads of the components are detected by TKEO. Finally, according to the difference in time to reach the measuring point between the initial wave heads of the line mode and zero mode components, the proportional relationship between the fault distance and the difference distance is written, and the double-ended traveling wave location formula independent of timing and wave velocity is obtained. A 220 kV transmission line fault simulation model is built using Matlab/Simulink. The simulation results show that the method has good applicability under noise, different ground resistances, and different fault types, and the accuracy of the location results is high.

    参考文献
    相似文献
    引证文献
引用本文

周 军,曲振国,战紫昂.基于CPO‑VMD的输电线路行波故障测距方法[J].电力科学与技术学报,2025,40(2):30-41.
ZHOU Jun, QU Zhenguo, ZHAN Ziang. Traveling wave fault location method of transmission line based on CPO‑VMD[J]. Journal of Electric Power Science and Technology,2025,40(2):30-41.