Study on electrical features of inter‑turn insulation fault of 10 kV dry‑type air‑core series reactor by field‑circuit coupling method
Author:
Affiliation:

(1.Hunan Extra High Voltage Substation Company, State Grid Hunan Electric Power Co., Ltd., Changsha 410004, China; 2.Chenzhou Power Supply Company, State Grid Hunan Electric Power Co., Ltd., Chenzhou 423000, China)

  • 摘要
  • | |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • | |
  • 文章评论
    摘要:

    并联电容器成套装置中干式空心串联电抗器匝间短路故障频发,严重威胁电力系统安全稳定运行,研究干式空心串联电抗器匝间短路前后的特征量变化具有重要意义。先采用ANSYS Maxwell数值软件,建立场路耦合模型,并将解析法计算值与厂家试验值进行对比,验证该模型准确性;再在此基础上构建匝间短路模型,对不同位置、不同阶段(匝间绝缘老化阶段、匝间短路阶段)的匝间绝缘故障电气量进行研究。研究结果表明,在匝间绝缘老化阶段及匝间短路阶段,各电气特征量的绝对值均随故障位置由端部向中部变化不断增大。其中,损耗因数和功率因数的变化率最大,故这两者可作为匝间短路故障在线监测的电气参量。

    Abstract:

    The frequent occurrence of inter-turn short circuit faults of dry-type air-core series reactors in shunt capacitor sets gravely imperils the secure and steady operation of the power system. It is extremely crucial to research the variations of characteristic quantities prior to and subsequent to inter-turn short circuits in dry-type air-core series reactors. In this paper, Maxwell is used to establish the field-circuit coupling model, and the model accuracy is verified by comparing the calculated value of the analytical method with the test value of the manufacturer. On this basis, the inter-turn short-circuit model is constructed, and the electrical quantities when inter-turn insulation faults occur at different locations in different phases (inter-turn insulation aging phase and inter-turn short-circuit phase) are investigated. The results show that the absolute value of each electrical characteristic quantity increases with the change of fault location from the end to the middle in the inter-turn insulation aging phase and the inter-turn short-circuit phase. In particular, the loss factor and power factor have the largest rates of change, which can be used as electrical parameters for on-line monitoring of inter-turn short-circuit faults.